You can only pull so far before the wire would try to stretch. You need a manhole every so often and possibly sectionalizers for when you splice sections if regular splices are not allowed.

Conduit can be bored to keep it deep but you have to come back up to hit the manholes.

Seen 13.8kV and 4160v require 300’ between manholes